=== Apcupsd ===
 
=== Apcupsd ===
[[http://www.apcupsd.org/|Apcupsd Apcupsd]] is software specifically for [http://apc.com Apc] Ups-es. The hardware link between the Ups and a server is (often) a Usb cable. Apc Ups-es come with an odd cable, with on one end a Usb connector and on the other end something that looks like a Utp connector. One server can be connected with the Ups. Other servers must be shutdown from that connected server.     
+
[http://www.apcupsd.org/ Apcupsd] is software specifically for [http://apc.com Apc] Ups-es. The hardware link between the Ups and a server is (often) a Usb cable. Apc Ups-es come with an odd cable, with on one end a Usb connector and on the other end something that looks like a Utp connector. One server can be connected with the Ups. Other servers must be shutdown from that connected server.     
  
 
=== Install ===
 
=== Install ===

Revision as of 15:24, 11 June 2015

Shutdown the servers before the Uninterruptible Power Supply is completely drained.

Use case

A Ups is great to avoid hard shutdowns of servers with short power cuts. But what if the power is interrupted for a longer time than the battery can provide the servers? For such cases there is software that shuts down the servers at a certain percentage of battery drainage.

Apcupsd

Apcupsd is software specifically for Apc Ups-es. The hardware link between the Ups and a server is (often) a Usb cable. Apc Ups-es come with an odd cable, with on one end a Usb connector and on the other end something that looks like a Utp connector. One server can be connected with the Ups. Other servers must be shutdown from that connected server.

Install

Apcupsd is in the non standard Epel repository.

yum install apcupsd

Connect the usb cable to the Ups and start the service and make it auto start at boot.

Run apcaccess to check if the Ups is found. It will display several parameters of the Ups.

Configure

The configuration files are in the directory
/etc/apcupsd
The most interesting variable in apcupsd.conf is
BATTERYLEVEL 50
Here it is set to initiate shutdown at 50% battery level.

Basically

Alternatives

Nut is a generic software, suitable for more Ups brands than Apc.